680 kW Prime Power Diesel Generator (Perkins Engine) (208/120V Three Phase 60Hz)

$0.00

Description

Amrocor Industrial Generator Set – Model 2806C-E18TTAG7

The Amrocor Industrial Generator Set is a fully integrated, high-performance power generation solution designed for standby, prime, and continuous power applications. Built for versatility, reliability, and optimum efficiency, it meets the demands of various industrial and commercial settings.


Core Components

  • Perkins Engine: Known for its durability and fuel efficiency.
  • Stamford CSA Approved Alternator: Ensures smooth, brushless power output.
  • Deepsea Control Panel: Provides real-time monitoring and fault management.

Key Features

  • Remote Wi-Fi Controller: Simplified system control and monitoring from any location.
  • Advanced Brushless Alternator: Next-generation technology with CSA certification.
  • Inbuilt Coolant Heater: Reduces cold starts and extends engine life.
  • Silent Weatherproof Enclosure: Reduces operational noise and protects against environmental challenges.
  • 8-Hour Dual Wall Fuel Tank: Supports extended, uninterrupted operation.
  • Electronic Speed Governor: Delivers stable performance under load variations.

Power Ratings

  • Prime Power: Ideal for continuous operation under variable loads, with a 10% overload allowance for 1 hour within 12 hours.
  • Standby Power: Designed for backup during power outages; no overload permitted.

Technical Specifications

Perkins Engine Details

Attribute Details
Model 2806C-E18TTAG7
Manufacturer Perkins
Cylinders 6 Cylinders in line
Cycle 4-Stroke
Aspiration Parallel Turbocharged, Air-to-Air Chargecooled
Bore x Stroke (mm) 145 x 183
Displacement 18.1 L
Compression Ratio 14:1
Prime Power 747 kW @ 1800 rpm
Standby Power 821 kW @ 1800 rpm
Cooling System Forced Liquid Cooling Cycle
Coolant Capacity 210 L
Fuel Consumption 212 g/kWh @ 100% Load

Stamford Alternator Details

Attribute Details
Model HCI634 CSA Approved
Power 680 kW
Frequency 60 Hz
Exciter Type Single Bearing, Brushless, Self-Excited
Voltage Regulation ≤+1%
Insulation Grade H
Protection Grade IP23
Phase 3

Deepsea Control Panel

  • Model: DSE
  • Monitors:
    • Generator Voltage
    • Output Frequency
    • Engine Speed
    • Battery Voltage
    • Engine Runtime
  • Fault Indicators:
    • Overspeed/Underspeed
    • Low Oil Pressure
    • High Water Temperature
    • Failure to Start
    • Battery Charger Failure
  • Automatic Shutdowns:
    • Low Oil Pressure
    • High Water Temperature
    • Overspeed/Underspeed

Testing & Compliance

  • Comprehensive load tests at 50%, 75%, 100%, and 110% capacity.
  • Fully compliant with ISO8528, GB2820, NEC, and CEC standards.

Applications

  • Prime Power: Continuous power for construction, industrial operations, and remote sites.
  • Standby Power: Backup energy for critical infrastructure such as hospitals, data centers, and businesses.
  • Continuous Power: Ideal for off-grid or high-demand environments.

The Amrocor 2806C-E18TTAG7 Generator Set is a robust and efficient energy solution tailored for a range of demanding applications, delivering reliable power when you need it most.

Delivery Notice

We process all orders within 24 hours of confirmation. Production times vary depending on the product and specific order requirements. To receive the most accurate lead time, please email us before placing your order so we can provide detailed information.

As a general guideline, estimated production times are as follows:

Oil: 6-8 weeks
Generators: 16-20 weeks
Transformers: 8-12 weeks
Switchgears: 8-12 weeks
Industrial Equipment: 8-12 weeks
Wiring & Cables: 2-4 weeks

While we strive to meet the estimated timelines, unforeseen factors may affect production and delivery schedules. We will make every effort to keep you updated throughout the process to ensure a smooth experience.

By placing an order, you agree to our terms and conditions, including any applicable production and shipping policies.

Request Quote