700 kW Standby Diesel Generator (Volvo Engine) (120/240V Single Phase 60Hz)

$0.00

Description

Amrocor Industrial Generator Sets

Amrocor industrial generator sets are fully integrated power generation systems that provide optimum performance, dependability, and versatility for standby power, prime power, and continuous power applications.


Powered By

  • Volvo Engine
  • Stamford Alternator
  • Deepsea Control Panel

Included Features

  • Technologically Advanced Remote WiFi Controller
  • Next-Generation Brushless Stamford CSA Approved Alternator
  • Inbuilt Webasto-Style Coolant Heater: Prevents cold starts and increases engine longevity.
  • Silent Soundproof Weather Protection Canopy/Enclosure
  • Standard 8-Hour Dual Wall Base Fuel Tank
  • Electronic Speed Governor

Power Ratings

  • Prime Power: Continuous electrical power supply at variable load with no limit on annual operating hours. Includes 10% overload capability for 1 hour in 12 hours.
  • Standby Power: Continuous power supply during utility power failures. Overload is not permitted.

Features

  • Comprehensive testing under varying load conditions: 50%, 75%, 100%, and 110%.
  • Verification of all control and safety shut-down functions.
  • Equipped with:
    • 24V DC Start Motor
    • 24V High-Performance Maintenance-Free Lead-Acid Starting Batteries
    • Industrial Silencer and Flexible Exhaust Hose
  • Designed to comply with ISO8528/GB2820, NEC, and CEC standards.

Technical Specifications

Volvo Engine Data

Attribute Specification
Model TWD1744GE
Manufacturer Volvo
Number of Cylinders 6 Cylinders Inline
Cycle 4-Stroke
Aspiration Wastegate Turbocharged
Bore x Stroke (mm) 149 x 165
Displacement 17.26 L
Compression Ratio 16.5:1
Prime Power / Speed 682 kW/1800rpm
Standby Power / Speed 750 kW/1800rpm
Speed Governor ECM
Cooling System Forced Liquid Cooling Cycle
Steady Speed Drop ≤1%
Lubrication Capacity 58 L
Fuel Consumption (75% Load) 197 g/kW h
Starter Motor DC24V
Alternator DC24V

Stamford Alternator Data

Attribute Specification
Model HCI544 (UL/CSA Approved)
Power 700 kW
Frequency/Speed 60Hz/1800rpm
Exciter Type Single Bearing, Brushless, Self-Excited
Power Factor 0.8
Voltage Adjust Range ≥5%
Voltage Regulation NL-FL ≤+1%
Insulation Grade H
Protection Grade IP23
Phase 1

Deepsea Control Panel Data

Attribute Specification
Model DSE (UL/CSA Approved)
Digital Displays Generator voltage, output frequency, engine speed, battery voltage, runtime
Failure Indicators Overspeed/underspeed, emergency stop, low oil pressure, high water temperature, battery charger failure
Automatic Shutdown Triggers Low engine oil pressure, high engine water temperature, overspeed/underspeed, failure to start after three attempts

 

Delivery Notice

We process all orders within 24 hours of confirmation. Production times vary depending on the product and specific order requirements. To receive the most accurate lead time, please email us before placing your order so we can provide detailed information.

As a general guideline, estimated production times are as follows:

Oil: 6-8 weeks
Generators: 16-20 weeks
Transformers: 8-12 weeks
Switchgears: 8-12 weeks
Industrial Equipment: 8-12 weeks
Wiring & Cables: 2-4 weeks

While we strive to meet the estimated timelines, unforeseen factors may affect production and delivery schedules. We will make every effort to keep you updated throughout the process to ensure a smooth experience.

By placing an order, you agree to our terms and conditions, including any applicable production and shipping policies.

Request Quote